MDA900Iss1.pdf
(
57 KB
)
Pobierz
EF
Installation Guide
MDA900
Parallel 24 Pulse Interbridge Lockout
Circuit
Part Number: 0410-0014
Issue Number: 1
www.controltechniques.com
General Information
The manufacturer accepts no liability for any consequences resulting from inappro-
priate, negligent or incorrect installation or adjustment of the optional operating pa-
rameters of the equipment or from mismatching the variable speed drive (drive) with
the motor.
Thecontentsofthisguidearebelievedtobecorrectatthetimeofprinting. Inthe
interests of a commitment to a policy of continuous development and improvement,
the manufacturer reserves the right to change the specification of the product or its
performance, or the contents of the guide, without notice.
All rights reserved. No parts of this guide may be reproduced or transmitted in any
form or by any means, electrical or mechanical including photocopying, recording or
by an information storage or retrieval system, without permission in writing from the
publisher.
Copyright
© December 2001 Control Techniques Drives Limited
Issue Code:
1
Contents
1
Introduction
1
1.1
Circuit Function
1
2
Electrical Installation
2
2.1
Terminal Description
2
3
Mechanical Installation
4
MDA900 User Guide
Issue Number: 1
1
I tr cti n
It is possible to extend the 12 pulse function of the Mentor drives to provide a 24 pulse
system by supplying two parallel 12 pulse systems from a transformer with four phase
shifted windings as shown in Figure 1.1 below.
24 Pulse system
power circuit wiring
0
o
30
o
15
o
45
o
E1
E2 E3
L1 L2 L3
E1
E2 E3
L1 L2 L3
E1
E2 E3
L1 L2 L3
E1
E2 E3
L1 L2 L3
Mentor
Drive 1
Mentor
Drive 2
Mentor
Drive 3
Mentor
Drive 4
A2
A1
A2
A1
A2
A1
A2
A1
IBR
IBR
IBR
M
Figure 1.1 System Overview
IBR = inter-bridge reactor
If any further information is required on 12 pulse systems, refer to the document
Mentor
12 Pulse and 24 Pulse Systems
which is available from the supplier of the drive.
1.1
Circuit Function
The drives should be programmed and connected for parallel 12 pulse operation, there
are no additional parameters to be set for 24 pulse operation.
If the drives are four quadrant then some extra logic is needed to control the bridge
interlocking.
The function of the circuit is to monitor which bridge is operating on each drive using
digital outputs on each drive. If any one drive tries to change bridge this circuit will
prevent the bridge changeover taking place until all of the drives are in a state which
allows a bridge changeover safely.
1
MDA900 User Guide
www.controltechniques.com
Issue Number: 1
2
Electrical Installation
2.1
Terminal Description
Connector
Terminal number
Description
1
24V supply
2
0V
PL1 (Slave 3)
3
ST5 input
4
F10 output
1
24V supply
2
0V
PL2 (Master)
3
ST5 input
4
F10 output
1
24V supply
2
0V
PL3 (Slave 1)
3
ST5 input
4
F10 output
1
24V supply
2
0V
PL4 (Slave 2)
3
ST5 input
4
F10 output
MDA900 Iss.00.00
SIDE 1
CONTROL TECHNIQUES LTD
3130-0574
7004-1033
IC3
PARALLEL 24 PULSE INTERBRIDGE LOCKOUT CIRCUIT
C5
Output
St at u s
IC2
C6
IC1
1
PL2
4
1
PL3
4
1
PL4
4
1
PL1
4
Figure 2.1 MDA900 Board Layout
2
MDA900 User Guide
Issue Number: 1
www.controltechniques.com
Plik z chomika:
fallen09
Inne pliki z tego folderu:
DNetiss1.pdf
(541 KB)
FXM5UG(Iss5).pdf
(481 KB)
INTERB3.PDF
(333 KB)
MD29Iss4.pdf
(1386 KB)
MD900Addendum1.pdf
(22 KB)
Inne foldery tego chomika:
software
Zgłoś jeśli
naruszono regulamin