Installation and Servicing
Instructions
Alpha CD50
Wall Mounted, Fan Assisted, Room Sealed, Gas Fired,
High Efficiency, Condensing Combination Boiler with
Unvented Hot Water Storage
For Technical help or for Service call ...
ALPHA HELPLINE
Tel: 0870 3001964
Nepicar House, London Road,
Wrotham Heath, Sevenoaks,
Kent TN15 7RS
Service Listed
Alpha CD50
G.C. No. 47 532 24
For use with Natural Gas only
Leave these instructions with the User
856368169.131.png 856368169.142.png 856368169.153.png 856368169.164.png 856368169.001.png 856368169.012.png 856368169.023.png
CONTENTS
1
Introduction ....................................... 2
7
Routine servicing ............................... 24
2
Technical data ................................... 3
8
Component replacement ................... 26
3
General boiler information .................. 7
9
Wiring diagrams ................................ 33
4
Installation ......................................... 14
10
Fault Finding ..................................... 35
5
Commissioning ................................. 20
11
Short parts list ................................... 39
6
Boiler operation ................................. 23
12
Service history .................................. 40
1
INTRODUCTION
The Alpha CD50 is a wall mounted, high efficiency, fan assisted, room-sealed, condensing combination boiler - incorporating a
52 litre unvented hot water storage cylinder. The burner is lit electronically and the heat output is controlled by a modulating
fan and gas valve.
The boiler, providing both central heating and domestic hot water at mains pressure, is designed for use with a fully pumped,
sealed and pressurised heating system using only Natural Gas .
The boiler is supplied with a pump, diverter valve, pressure relief valve, expansion vessel and pressure gauge fully assembled
and tested.
As supplied, the boiler will automatically modulate to provide central heating outputs between 6.3 and 29.7 kW (21 500 and
101 430 Btu/h).
The maximum output available for domestic hot water is 32.0 kW (109 200 Btu/h) and provides hot water at temperatures of up
to 65°C and flow rates of up to 18 litres/min (4 gal/min).
IMPORTANT
This boiler has been approved to the Building Regulations for unvented hot water storage systems and the Local Authority
must be notified of the intention to install. Therefore the installation must be carried out by a person competent to install
unvented hot water systems.
It is the law that all gas appliances are installed by a competent person, ie CORGI registered personnel, in accordance with
the following recommendations:-
Gas Safety (Installation and Use) Regulations 1984 (as amended)
All current Building Regulations issued by the Department of the Environment, i.e. Approved Document L1
Building Standards (Scotland) (Consolidation) Regulations issued by the Scottish Development Department
Local Water Bye Laws
Health & Safety Document No. 635 (The Electricity At Work Regulations 1989)
The installation should also be in accordance with the following British Standard Codes of Practice:-
BS 5440:1:2000 Flues
BS 5449:1990 Forced circulation hot water systems
BS 5546:2000 Installation of hot water supplies for domestic purposes
BS 6700:1997 Design, installation, testing and maintenance of services supplying water
BS 6798:2000 Installation of gas fired hot water boilers
BS 6891:1998 Gas installation
BS 7593:1992 Code of Practice for treatment of water in heating systems
BS 7671:2001 Requirements for electrical installations, IEE Wiring Regulations
If installation is in a timber framed building, refer to the Institute of Gas Engineers document IGE/UP/7.
This appliance meets the requirements of IPX4D, ie degree of protection against moisture.
Failure to install this appliance correctly could lead to prosecution. It is in your own interest and that of safety to ensure that the
law is complied with.
Manufacturer's instructions must NOT be taken in anyway as over-riding statutory obligations.
Notes: 1. Ensure that the Benchmark Log Book has been completed after the boiler has been installed and commissioned.
2. Ensure that the appliance has been supplied with an Alpha CD flue system.
2
Alpha CD50 - Contents/Introduction
856368169.034.png 856368169.045.png
2
TECHNICAL DATA
2.1
PERFORMANCE - NATURAL GAS
Central Heating
Heat Input (H s ) kW
(Gross) Btu/h
Heat Input (H i ) kW
(Net) Btu/h
Heat Output (H s condensing) kW
(50°C/30°C) Btu/h
Heat Output (H i non-condensing) kW
(80°C/60°C)
MAX.
31.0
105 770
28.0
95 230
29.7
101 430
27.6
94 130
2.91
1.16
2.95
104.1
MIN.
7.4
25 360
6.6
22 830
7.0
23 980
6.5
21 500
0.27
0.11
0.71
25.1
Domestic Hot Water
Heat Input (H s )
MAX.
36.1
123 190
32.6
110 910
32.0
109 200
3.70
1.48
3.44
121.4
18.0
4.0
65
149
MIN.
7.4
25 360
6.6
22 830
6.3
21 500
0.27
0.11
0.71
25.1
1.0
0.22
5
41
kW
(Gross)
Btu/h
Heat Input (H i )
kW
(Net)
Btu/h
Output to Water (H s )
kW
(modulating)
Btu/h
Differential Burner
mbar
Room sealed
chamber panel
fitted
Btu/h
Pressure
in wg
Differential Burner
mbar
Gas Rate
m³/h
ft³/h
Room sealed
chamber panel
fitted
Pressure
in wg
Gas Rate
m³/h
ft³/h
Flow Rate
L/min
G.P.M.
Outlet Water Temp. (Approx.)
°C
°F
Time to raise water store by 50°C
Reheat time for 70% of store
7 minutes
3 minutes
5 minutes
(boiler ON)
(boiler OFF)
2.2
SYSTEM
Central Heating (Sealed System)
Max. Working System Pressure
Min. System Pressure
Max. System temperature
Pressure Relief Valve Setting
Expansion Vessel Size (pre-charge press.)
Flow Connection
Return Connection
Relief Valve Connection
Recommended System Pressure (cold)
CH Water Temp. (Approx. max.)
Domestic Hot Water
Max. Hot Water Working Pressure
Max. Mains Inlet Pressure (inlet of pressure reducing valve)
Min. Mains Water Pressure
Mains Inlet Connection
DHW Outlet Connection
DHW Water Storage
Expansion Vessel Size (pre-charge press.)
Pressure Reducing Valve Setting
Temperature and Pressure Relief Valve
Expansion Relief Valve Setting
2.5 bar
0.5 bar
82°C
3 bar (44 PSI)
8 L at 0.8 bar
22 mm
22 mm
15 mm
1.0 bar
82°C (180°F)
5.5 bar
12 bar
0.1 bar
15 mm
15 mm
52 L
4 L at 2.5 bar
2.5 bar
90°C/7 bar
6 bar
2.3
COMPONENTS
2.4
ELECTRICAL
Burner
Main Heat Exchanger
DHW Storage Cylinder
Main Burner Injector
Flue - Outer Duct
Flue - Inner Duct
Stainless steel
Stainless steel
Stainless Steel
6.6 mm
White
Plastic
Supply
External Fuse
Power Consumption
Internal Fuse
Electrode Spark Gap
230/240 V ~ 50 Hz
3 A
140 W
F2 A
3 - 4 mm
2.5
INSTALLATION
2.6
GENERAL
Min. Clearances for Servicing
Top
220 mm
250 mm
10 mm
450 mm
100 mm Dia.
100 mm
110 mm Dia.
70 kg
130 kg
Case Dimensions
Height
Width
Depth
900 mm
600 mm
450 mm
22 mm
3.2 L
100 mm
60 mm
(from casing)
Bottom
Sides
Front
Gas Connection
Primary Water Content
Air Duct Diameter
Flue Duct Diameter
Flue Terminal Size
Flue Terminal Protruding
Hole Size Required For Flue Assy.
Lift Weight
Weight Full and Operational
Alpha CD50 - Technical Data
3
856368169.056.png 856368169.067.png 856368169.078.png
 
2.7 FLUE LENGTHS
CD Easy-Flue 500 mm with terminal and 90° bend. A CD Easy-Flue 1000 mm with terminal and 90° bend is also available.
CD 750 mm flue extensions are available.
Length of Flue Required:-
Rear Flue = wall thickness + 170 mm (includes terminal)
Side Flue = wall thickness + distance between wall and side of boiler + 230 mm (includes terminal)
Vertical Flue = distance from top of boiler side panel to required roof position minus 1 m for vertical terminal assembly
Maximum horizontal flue length = 12 m.
Maximum vertical flue length including terminal is 15 m.
Each additional CD 90° Bend is equivalent to 1.3 m of flue length.
Each CD 45° Bend is equivalent to 0.9 m of flue length.
The CD Vertical Flue terminal assembly is equivalent to 1 m of flue length.
2.8
AVAILABLE PUMP HEAD FOR CENTRAL HEATING
Output (50/30°C)
Available pump head
Flow rate
kW
Btu/h
20°C
20°C
metres
2.3
3.5
feet
7.6
11.6
litre/min
16.6
gal/min
3.7
25.40
18.70
15.60
12.35
86 700
64 000
53 000
42 200
12.6
10.5
8.3
3.2
2.8
2.3
1.8
0.7
3.8
4.0
4.6
12.6
13.2
15.2
5.30
18 100
This information is based on 20°C system design temperature difference.
Note: For outputs upto 30 kW refer to section 3.7.
2.9 ELECTRICAL CONNECTIONS
Note: This Appliance Must Be Earthed
An optional integral Clock kit is available if required.
Not
Used
Red
Wire
Red
Wire
Brown
Wire
Blue
Wire
5
4
3
2
1
Internal Clock Terminals
WARNING
1. Ensure wires are connected
correctly
2. Only fit the Alpha recommended
clock. Other clocks could cause
damage.
Clock connections
Boiler terminal block
Fig. 1
4
Alpha CD50 - Technical Data
856368169.091.png 856368169.092.png 856368169.093.png 856368169.094.png 856368169.095.png 856368169.096.png 856368169.097.png 856368169.098.png 856368169.099.png 856368169.100.png 856368169.101.png 856368169.102.png 856368169.103.png 856368169.104.png 856368169.105.png 856368169.106.png 856368169.107.png 856368169.108.png 856368169.109.png 856368169.110.png 856368169.111.png 856368169.112.png 856368169.113.png 856368169.114.png 856368169.115.png 856368169.116.png 856368169.117.png 856368169.118.png 856368169.119.png 856368169.120.png 856368169.121.png 856368169.122.png 856368169.123.png 856368169.124.png 856368169.125.png 856368169.126.png 856368169.127.png 856368169.128.png 856368169.129.png
 
2.10
BOILER SCHEMATIC
1
Flue sampling point
15
Automatic air vent
29
CH Pressure Relief Valve
2
Flue thermostat
16
Pump
30
DHW Expansion Vessel
3
Injector
17
Drain point
31
DHW Storage Temperature Sensor
4
Gas valve
18
Pressure gauge
32
DHW Temperature/Pressure Relief Valve
5
Primary temperature sensor
19
Primary pressure switch
33
Storage Cylinder
6
Venturi
20
Ignition electrodes
34
Secondary Heat Exchanger
7
Main burner
21
Flame sensing electrode
35
DHW Drain Point
8
Primary/condensing heat exchanger
22
Venturi negative point
36
DHW Expansion Relief Valve
9
Room sealed chamber
23
Venturi positive point
37
Mains Inlet Filter
10
Fan
24
Gas service cock
38
Check Valve
11
Pressure differential test points
25
On/off valve (2 off)
39
Mains Inlet Valve
12
Flue hood
26
Automatic by-pass
40
Pressure Reducing Valve with Filter
13
Overheat thermostat
27
Cyclone separator
41
Automatic Flow Regulator
14
CH Expansion vessel
28
Condensate trap
42
Tundish
43
Diverter Valve
Fig. 2
Alpha CD50 - Technical Data
5
856368169.130.png 856368169.132.png 856368169.133.png 856368169.134.png 856368169.135.png 856368169.136.png 856368169.137.png 856368169.138.png 856368169.139.png 856368169.140.png 856368169.141.png 856368169.143.png 856368169.144.png 856368169.145.png 856368169.146.png 856368169.147.png 856368169.148.png 856368169.149.png 856368169.150.png 856368169.151.png 856368169.152.png 856368169.154.png 856368169.155.png 856368169.156.png 856368169.157.png 856368169.158.png 856368169.159.png 856368169.160.png 856368169.161.png 856368169.162.png 856368169.163.png 856368169.165.png 856368169.166.png 856368169.167.png 856368169.168.png 856368169.169.png 856368169.170.png 856368169.171.png 856368169.172.png 856368169.173.png 856368169.174.png 856368169.002.png 856368169.003.png 856368169.004.png 856368169.005.png 856368169.006.png 856368169.007.png 856368169.008.png 856368169.009.png 856368169.010.png 856368169.011.png 856368169.013.png 856368169.014.png 856368169.015.png 856368169.016.png 856368169.017.png 856368169.018.png 856368169.019.png 856368169.020.png 856368169.021.png 856368169.022.png 856368169.024.png 856368169.025.png 856368169.026.png 856368169.027.png 856368169.028.png 856368169.029.png 856368169.030.png 856368169.031.png 856368169.032.png 856368169.033.png 856368169.035.png 856368169.036.png 856368169.037.png 856368169.038.png 856368169.039.png 856368169.040.png 856368169.041.png 856368169.042.png 856368169.043.png 856368169.044.png 856368169.046.png 856368169.047.png 856368169.048.png 856368169.049.png 856368169.050.png 856368169.051.png 856368169.052.png 856368169.053.png 856368169.054.png 856368169.055.png 856368169.057.png 856368169.058.png 856368169.059.png 856368169.060.png 856368169.061.png 856368169.062.png 856368169.063.png 856368169.064.png 856368169.065.png 856368169.066.png 856368169.068.png 856368169.069.png 856368169.070.png 856368169.071.png 856368169.072.png 856368169.073.png 856368169.074.png 856368169.075.png 856368169.076.png 856368169.077.png 856368169.079.png 856368169.080.png 856368169.081.png 856368169.082.png 856368169.083.png 856368169.084.png 856368169.085.png 856368169.086.png 856368169.087.png 856368169.088.png 856368169.089.png 856368169.090.png
 