EIG-H-LV-switchgear.pdf

(3024 KB) Pobierz
Chapter H
LV switchgear: functions &
selection
Contents
The basic functions of LV switchgear
H2
1.1 Electrical protection
H2
1.2 Isolation
H3
1.3 Switchgear control
H4
2
The switchgear
H5
2.1 Elementary switching devices
H5
2.2 Combined switchgear elements
H9
3
Choice of switchgear
H0
3.1 Tabulated functional capabilities
H10
3.2 Switchgear selection
H10
4
Circuit-breaker
H
4.1 Standards and description
H11
4.2 Fundamental characteristics of a circuit-breaker
H13
4.3 Other characteristics of a circuit-breaker
H15
4.4 Selection of a circuit-breaker
H18
H
4.5 Coordination between circuit-breakers
H22
4.6 Discrimination MV/LV in a consumer’s substation
H28
Schneider Electric - Electrical installation guide 2008
1055456748.049.png 1055456748.060.png 1055456748.062.png 1055456748.063.png 1055456748.001.png 1055456748.002.png 1055456748.003.png 1055456748.004.png 1055456748.005.png 1055456748.006.png 1055456748.007.png 1055456748.008.png 1055456748.009.png 1055456748.010.png 1055456748.011.png 1055456748.012.png
 
The basic functions of
LV switchgear
H - LV switchgear: functions & selection
National and international standards deine the manner in which electric circuits of
LV installations must be realized, and the capabilities and limitations of the various
switching devices which are collectively referred to as switchgear.
The main functions of switchgear are:
b Electrical protection
b Electrical isolation of sections of an installation
b Local or remote switching
These functions are summarized below in Figure H .
Electrical protection at low voltage is (apart from fuses) normally incorporated in
circuit-breakers, in the form of thermal-magnetic devices and/or residual-current-
operated tripping devices (less-commonly, residual voltage- operated devices
- acceptable to, but not recommended by IEC).
In addition to those functions shown in Figure H1, other functions, namely:
b Over-voltage protection
b Under-voltage protection
are provided by speciic devices (lightning and various other types of voltage-surge
arrester, relays associated with contactors, remotely controlled circuit-breakers, and
with combined circuit-breaker/isolators… and so on)
The role of switchgear is:
b Electrical protection
b Safe isolation from live parts
b Local or remote switching
Electrical protection
Isolation
Control
against
b Overload currents
b Isolation clearly indicated
b Functional switching
H2
b Short-circuit currents
by an authorized fail-proof
b Emergency switching
b Insulation failure
mechanical indicator
b Emergency stopping
b A gap or interposed insulating
b Switching off for
barrier between the open
mechanical maintenance
contacts, clearly visible
Fig. H1 : Basic functions of LV switchgear
. Electrical protection
Electrical protection assures:
b Protection of circuit elements against the
thermal and mechanical stresses of short-circuit
currents
b Protection of persons in the event of
insulation failure
b Protection of appliances and apparatus being
supplied (e.g. motors, etc.)
The aim is to avoid or to limit the destructive or dangerous consequences of
excessive (short-circuit) currents, or those due to overloading and insulation failure,
and to separate the defective circuit from the rest of the installation.
A distinction is made between the protection of:
b The elements of the installation (cables, wires, switchgear…)
b Persons and animals
b Equipment and appliances supplied from the installation
The protection of circuits
v Against overload; a condition of excessive current being drawn from a healthy
(unfaulted) installation
v Against short-circuit currents due to complete failure of insulation between
conductors of different phases or (in TN systems) between a phase and neutral (or
PE) conductor
Protection in these cases is provided either by fuses or circuit-breaker, in the
distribution board at the origin of the inal circuit (i.e. the circuit to which the load
is connected). Certain derogations to this rule are authorized in some national
standards, as noted in chapter H1 sub-clause 1.4.
The protection of persons
v Against insulation failures. According to the system of earthing for the installation
(TN, TT or IT) the protection will be provided by fuses or circuit-breakers, residual
current devices, and/or permanent monitoring of the insulation resistance of the
installation to earth
The protection of electric motors
v Against overheating, due, for example, to long term overloading, stalled rotor,
single-phasing, etc. Thermal relays, specially designed to match the particular
characteristics of motors are used.
Such relays may, if required, also protect the motor-circuit cable against overload.
Short-circuit protection is provided either by type aM fuses or by a circuit-breaker
from which the thermal (overload) protective element has been removed, or
otherwise made inoperative.
Schneider Electric - Electrical installation guide 2008
1055456748.013.png 1055456748.014.png 1055456748.015.png 1055456748.016.png 1055456748.017.png 1055456748.018.png 1055456748.019.png 1055456748.020.png 1055456748.021.png 1055456748.022.png 1055456748.023.png
The basic functions of
LV switchgear
H - LV switchgear: functions & selection
.2 Isolation
A state of isolation clearly indicated by an
approved “fail-proof” indicator, or the visible
separation of contacts, are both deemed to
satisfy the national standards of many countries
The aim of isolation is to separate a circuit or apparatus (such as a motor, etc.) from
the remainder of a system which is energized, in order that personnel may carry out
work on the isolated part in perfect safety.
In principle, all circuits of an LV installation shall have means to be isolated.
In practice, in order to maintain an optimum continuity of service, it is preferred to
provide a means of isolation at the origin of each circuit.
An isolating device must fulil the following requirements:
b All poles of a circuit, including the neutral (except where the neutral is a PEN
conductor) must open (1)
b It must be provided with a locking system in open position with a key (e.g. by
means of a padlock) in order to avoid an unauthorized reclosure by inadvertence
b It must comply with a recognized national or international standard
(e.g. IEC 60947-3) concerning clearance between contacts, creepage distances,
overvoltage withstand capability, etc.:
Other requirements apply:
v Veriication that the contacts of the isolating device are, in fact, open.
The veriication may be:
- Either visual, where the device is suitably designed to allow the contacts to be seen
(some national standards impose this condition for an isolating device located at the
origin of a LV installation supplied directly from a MV/LV transformer)
- Or mechanical, by means of an indicator solidly welded to the operating shaft
of the device. In this case the construction of the device must be such that, in the
eventuality that the contacts become welded together in the closed position, the
indicator cannot possibly indicate that it is in the open position
v Leakage currents. With the isolating device open, leakage currents between the
open contacts of each phase must not exceed:
- 0.5 mA for a new device
- 6.0 mA at the end of its useful life
v Voltage-surge withstand capability, across open contacts. The isolating device,
when open must withstand a 1.2/50 μ s impulse, having a peak value of 6, 8 or 12 kV
according to its service voltage, as shown in Figure H2 . The device must satisfy
these conditions for altitudes up to 2,000 metres. Correction factors are given in
IEC 60664-1 for altitudes greater than 2,000 metres.
Consequently, if tests are carried out at sea level, the test values must be increased
by 23% to take into account the effect of altitude. See standard IEC 60947.
H3
Service (nominal
Impulse withstand
voltage
peak voltage category
(V)
(for 2,000 metres)
(kV)
III
IV
230/400
4
6
400/690
6
8
690/1,000
8
12
Fig. H2 : Peak value of impulse voltage according to normal service voltage of test specimen.
The degrees III and IV are degrees of pollution deined in IEC 60664-1
(1) the concurrent opening of all live conductors, while not
always obligatory, is however, strongly recommended (for
reasons of greater safety and facility of operation). The neutral
contact opens after the phase contacts, and closes before
them (IEC 60947-1).
Schneider Electric - Electrical installation guide 2008
1055456748.024.png 1055456748.025.png 1055456748.026.png 1055456748.027.png 1055456748.028.png 1055456748.029.png 1055456748.030.png 1055456748.031.png 1055456748.032.png 1055456748.033.png 1055456748.034.png 1055456748.035.png
The basic functions of
LV switchgear
H - LV switchgear: functions & selection
.3 Switchgear control
Switchgear-control functions allow system
operating personnel to modify a loaded system
at any moment, according to requirements,
and include:
b Functional control (routine switching, etc.)
b Emergency switching
b Maintenance operations on the power system
In broad terms “control” signiies any facility for safely modifying a load-carrying
power system at all levels of an installation. The operation of switchgear is an
important part of power-system control.
Functional control
This control relates to all switching operations in normal service conditions for
energizing or de-energizing a part of a system or installation, or an individual piece
of equipment, item of plant, etc.
Switchgear intended for such duty must be installed at least:
b At the origin of any installation
b At the inal load circuit or circuits (one switch may control several loads)
Marking (of the circuits being controlled) must be clear and unambiguous.
In order to provide the maximum lexibility and continuity of operation, particularly
where the switching device also constitutes the protection (e.g. a circuit-breaker or
switch-fuse) it is preferable to include a switch at each level of distribution, i.e. on
each outgoing way of all distribution and subdistribution boards.
The manœuvre may be:
b Either manual (by means of an operating lever on the switch) or
b Electric, by push-button on the switch or at a remote location (load-shedding and
reconnection, for example)
These switches operate instantaneously (i.e. with no deliberate delay), and those
that provide protection are invariably omni-polar (1) .
The main circuit-breaker for the entire installation, as well as any circuit-breakers
used for change-over (from one source to another) must be omni-polar units.
H4
Emergency switching - emergency stop
An emergency switching is intended to de-energize a live circuit which is, or could
become, dangerous (electric shock or ire).
An emergency stop is intended to halt a movement which has become dangerous.
In the two cases:
b The emergency control device or its means of operation (local or at remote
location(s)) such as a large red mushroom-headed emergency-stop pushbutton must
be recognizable and readily accessible, in proximity to any position at which danger
could arise or be seen
b A single action must result in a complete switching-off of all live conductors (2) (3)
b A “break glass” emergency switching initiation device is authorized, but in
unmanned installations the re-energizing of the circuit can only be achieved by
means of a key held by an authorized person
It should be noted that in certain cases, an emergency system of braking, may
require that the auxiliary supply to the braking-system circuits be maintained until
inal stoppage of the machinery.
Switching-off for mechanical maintenance work
This operation assures the stopping of a machine and its impossibility to be
inadvertently restarted while mechanical maintenance work is being carried out
on the driven machinery. The shutdown is generally carried out at the functional
switching device, with the use of a suitable safety lock and warning notice at the
switch mechanism.
(1) One break in each phase and (where appropriate) one
break in the neutral.
(2) Taking into account stalled motors.
(3) In a TN schema the PEN conductor must never be
opened, since it functions as a protective earthing wire as well
as the system neutral conductor.
Schneider Electric - Electrical installation guide 2008
1055456748.036.png 1055456748.037.png 1055456748.038.png
 
2 The switchgear
H - LV switchgear: functions & selection
2.1 Elementary switching devices
Disconnector (or isolator) (see Fig. H )
This switch is a manually-operated, lockable, two-position device (open/closed)
which provides safe isolation of a circuit when locked in the open position. Its
characteristics are deined in IEC 60947-3. A disconnector is not designed to make
or to break current (1) and no rated values for these functions are given in standards.
It must, however, be capable of withstanding the passage of short-circuit currents
and is assigned a rated short-time withstand capability, generally for 1 second,
unless otherwise agreed between user and manufacturer. This capability is normally
more than adequate for longer periods of (lower-valued) operational overcurrents,
such as those of motor-starting. Standardized mechanical-endurance, overvoltage,
and leakage-current tests, must also be satisied.
Load-breaking switch (see Fig. H6 )
This control switch is generally operated manually (but is sometimes provided with
electrical tripping for operator convenience) and is a non-automatic two-position
device (open/closed).
It is used to close and open loaded circuits under normal unfaulted circuit conditions.
It does not consequently, provide any protection for the circuit it controls.
IEC standard 60947-3 deines:
b The frequency of switch operation (600 close/open cycles per hour maximum)
b Mechanical and electrical endurance (generally less than that of a contactor)
b Current making and breaking ratings for normal and infrequent situations
When closing a switch to energize a circuit there is always the possibility that
an unsuspected short-circuit exists on the circuit. For this reason, load-break
switches are assigned a fault-current making rating, i.e. successful closure against
the electrodynamic forces of short-circuit current is assured. Such switches are
commonly referred to as “fault-make load-break” switches. Upstream protective
devices are relied upon to clear the short-circuit fault
Category AC-23 includes occasional switching of individual motors. The switching
of capacitors or of tungsten ilament lamps shall be subject to agreement between
manufacturer and user.
The utilization categories referred to in Figure H7 do not apply to an equipment
normally used to start, accelerate and/or stop individual motors.
Example
A 100 A load-break switch of category AC-23 (inductive load) must be able:
b To make a current of 10 I n (= 1,000 A) at a power factor of 0.35 lagging
b To break a current of 8 I n (= 800 A) at a power factor of 0.45 lagging
b To withstand short duration short-circuit currents when closed
H
Fig. H5 : Symbol for a disconnector (or isolator)
Fig. H6 : Symbol for a load-break switch
Cos ϕ
Utilization category
Typical applications
Making
Breaking
current x I n
current x I n
Frequent
Infrequent
operations
operations
AC-20A
AC-20B
Connecting and disconnecting
-
-
-
under no-load conditions
AC-21A
AC-21B
Switching of resistive loads
0.95
1.5
1.5
including moderate overloads
AC-22A
AC-22B
Switching of mixed resistive
0.65
3
3
and inductive loads, including
moderate overloads
0.45 for I y 100 A
AC-23A
AC-23B
Switching of motor loads or
10
8
0.35 for I > 100 A
other highly inductive loads
Fig. H7 : Utilization categories of LV AC switches according to IEC 60947-3
(1) i.e. a LV disconnector is essentially a dead system
switching device to be operated with no voltage on either side
of it, particularly when closing, because of the possibility of an
unsuspected short-circuit on the downstream side. Interlocking
with an upstream switch or circuit-breaker is frequently used.
Schneider Electric - Electrical installation guide 2008
1055456748.039.png 1055456748.040.png 1055456748.041.png 1055456748.042.png 1055456748.043.png 1055456748.044.png 1055456748.045.png 1055456748.046.png 1055456748.047.png 1055456748.048.png 1055456748.050.png 1055456748.051.png 1055456748.052.png 1055456748.053.png 1055456748.054.png 1055456748.055.png 1055456748.056.png 1055456748.057.png 1055456748.058.png 1055456748.059.png 1055456748.061.png
 
Zgłoś jeśli naruszono regulamin